Trane furnace display-code reference

Use the full installer’s guide and its cover model list. These codes do not apply to every Trane furnace or replacement control.

TRANE / FURNACE / MANUAL-SCOPED PILOT

18-CE16D1-1C-EN · S8B1 / S8X1 / S8X2

This installer’s guide lists S8B1 / S8X1 single-stage and S8X2 two-stage cover models. The full model list and suffixes are on the cover. A family prefix does not confirm applicability to an installed control. Identify the full document in available paperwork; do not open equipment.

Open 18-CE16D1-1C-EN · cover models, page 1 → Edition April 2021; source accessed 2026-11-16. The supplied manual was visually inspected; exact installed applicability remains unconfirmed.

Seventeen Error Codes from Integrated Furnace Control Display Codes, printed / PDF page 58. These are segmented alphanumeric display codes, not flash counts. Decimal points are retained in readable notation; the PDF text layer misreads some display glyphs.

E3.3 and E3.4 apply only to S8X2. E11 alternatives (3)–(5) also exclude S8B1 and S8X1. Menu labels, operating states and fault-clearing instructions are outside this lookup. No reset or equipment test is requested.

  1. Code E01

    Loss of the IRQ or other internal failures (Internal IFC error)

    Listed S8B1/S8X1 single-stage and S8X2 two-stage cover models only. Exact installed model/revision/control applicability remains unconfirmed; cover model suffixes must be checked in available paperwork.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Error Codes table context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    18-CE16D1-1C-EN · edition April 2021 · printed / PDF page 58 · Integrated Furnace Control — Error Codes

    Return to Trane lookup → · Record observations for service →

  2. Code E2.1

    Retry Exceeded (Flame never sensed, one hour lockout after 3 times)

    Listed S8B1/S8X1 single-stage and S8X2 two-stage cover models only. Exact installed model/revision/control applicability remains unconfirmed; cover model suffixes must be checked in available paperwork.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Error Codes table context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    18-CE16D1-1C-EN · edition April 2021 · printed / PDF page 58 · Integrated Furnace Control — Error Codes

    Return to Trane lookup → · Record observations for service →

  3. Code E2.2

    Recycles Exceeded (Flame sensed then lost, one hour lockout after 10 times)

    Listed S8B1/S8X1 single-stage and S8X2 two-stage cover models only. Exact installed model/revision/control applicability remains unconfirmed; cover model suffixes must be checked in available paperwork.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Error Codes table context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    18-CE16D1-1C-EN · edition April 2021 · printed / PDF page 58 · Integrated Furnace Control — Error Codes

    Return to Trane lookup → · Record observations for service →

  4. Code E2.3

    1st Stage Gas Valve Not Energized When It Should Be exceeded after 10 times

    Listed S8B1/S8X1 single-stage and S8X2 two-stage cover models only. Exact installed model/revision/control applicability remains unconfirmed; cover model suffixes must be checked in available paperwork.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Error Codes table context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    18-CE16D1-1C-EN · edition April 2021 · printed / PDF page 58 · Integrated Furnace Control — Error Codes

    Return to Trane lookup → · Record observations for service →

  5. Code E3.1

    Shorted Pressure Switch, 1st Stage

    Listed S8B1/S8X1 single-stage and S8X2 two-stage cover models only. Exact installed model/revision/control applicability remains unconfirmed; cover model suffixes must be checked in available paperwork.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Error Codes table context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    18-CE16D1-1C-EN · edition April 2021 · printed / PDF page 58 · Integrated Furnace Control — Error Codes

    Return to Trane lookup → · Record observations for service →

  6. Code E3.2

    Open Pressure Switch, 1st Stage

    Listed S8B1/S8X1 single-stage and S8X2 two-stage cover models only. Exact installed model/revision/control applicability remains unconfirmed; cover model suffixes must be checked in available paperwork.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Error Codes table context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    18-CE16D1-1C-EN · edition April 2021 · printed / PDF page 58 · Integrated Furnace Control — Error Codes

    Return to Trane lookup → · Record observations for service →

  7. Code E3.3

    Shorted Pressure Switch, 2nd Stage (Not Applicable for S8B1, S8X1)

    S8X2 only; source explicitly excludes S8B1 and S8X1. Exact installed model/revision/control applicability remains unconfirmed; cover model suffixes must be checked in available paperwork.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Error Codes table context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    18-CE16D1-1C-EN · edition April 2021 · printed / PDF page 58 · Integrated Furnace Control — Error Codes

    Return to Trane lookup → · Record observations for service →

  8. Code E3.4

    Open Pressure Switch, 2nd Stage (Not Applicable for S8B1, S8X1)

    S8X2 only; source explicitly excludes S8B1 and S8X1. Exact installed model/revision/control applicability remains unconfirmed; cover model suffixes must be checked in available paperwork.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Error Codes table context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    18-CE16D1-1C-EN · edition April 2021 · printed / PDF page 58 · Integrated Furnace Control — Error Codes

    Return to Trane lookup → · Record observations for service →

  9. Code E04

    Open Limit (Main Thermal, Rollout Switch, or Reverse Airflow Switch)

    Listed S8B1/S8X1 single-stage and S8X2 two-stage cover models only. Exact installed model/revision/control applicability remains unconfirmed; cover model suffixes must be checked in available paperwork.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Error Codes table context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    18-CE16D1-1C-EN · edition April 2021 · printed / PDF page 58 · Integrated Furnace Control — Error Codes

    Return to Trane lookup → · Record observations for service →

  10. Code E05

    Flame detected, should not be present

    Listed S8B1/S8X1 single-stage and S8X2 two-stage cover models only. Exact installed model/revision/control applicability remains unconfirmed; cover model suffixes must be checked in available paperwork.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Error Codes table context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    18-CE16D1-1C-EN · edition April 2021 · printed / PDF page 58 · Integrated Furnace Control — Error Codes

    Return to Trane lookup → · Record observations for service →

  11. Code E6.1

    Voltage reversed polarity

    Listed S8B1/S8X1 single-stage and S8X2 two-stage cover models only. Exact installed model/revision/control applicability remains unconfirmed; cover model suffixes must be checked in available paperwork.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Error Codes table context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    18-CE16D1-1C-EN · edition April 2021 · printed / PDF page 58 · Integrated Furnace Control — Error Codes

    Return to Trane lookup → · Record observations for service →

  12. Code E6.2

    Bad grounding

    Listed S8B1/S8X1 single-stage and S8X2 two-stage cover models only. Exact installed model/revision/control applicability remains unconfirmed; cover model suffixes must be checked in available paperwork.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Error Codes table context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    18-CE16D1-1C-EN · edition April 2021 · printed / PDF page 58 · Integrated Furnace Control — Error Codes

    Return to Trane lookup → · Record observations for service →

  13. Code E6.3

    (1) Igniter relay fails; (2) Igniter open

    Listed S8B1/S8X1 single-stage and S8X2 two-stage cover models only. Exact installed model/revision/control applicability remains unconfirmed; cover model suffixes must be checked in available paperwork.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Error Codes table context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    18-CE16D1-1C-EN · edition April 2021 · printed / PDF page 58 · Integrated Furnace Control — Error Codes

    Return to Trane lookup → · Record observations for service →

  14. Code E7.1

    1st stage gas valve (MVL) is energized when it should be off

    Listed S8B1/S8X1 single-stage and S8X2 two-stage cover models only. Exact installed model/revision/control applicability remains unconfirmed; cover model suffixes must be checked in available paperwork.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Error Codes table context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    18-CE16D1-1C-EN · edition April 2021 · printed / PDF page 58 · Integrated Furnace Control — Error Codes

    Return to Trane lookup → · Record observations for service →

  15. Code E08

    Flame current is low, but still strong enough to allow operation

    Listed S8B1/S8X1 single-stage and S8X2 two-stage cover models only. Exact installed model/revision/control applicability remains unconfirmed; cover model suffixes must be checked in available paperwork.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Error Codes table context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    18-CE16D1-1C-EN · edition April 2021 · printed / PDF page 58 · Integrated Furnace Control — Error Codes

    Return to Trane lookup → · Record observations for service →

  16. Code E11

    (1) 1st stage gas valve not energized when it should be; (2) 1st stage gas valve relay stuck closed; (3) 2nd stage gas valve relay stuck closed (Not Applicable for S8B1, S8X1); (4) 2nd stage gas valve energized when it should not be (Not Applicable for S8B1, S8X1); (5) 2nd stage gas valve not energized when it should be (Not Applicable for S8B1, S8X1)

    Listed S8B1/S8X1 single-stage and S8X2 two-stage cover models only. E11 alternatives (3)–(5) apply only to S8X2. Exact installed model/revision/control applicability remains unconfirmed; cover model suffixes must be checked in available paperwork.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Error Codes table context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    18-CE16D1-1C-EN · edition April 2021 · printed / PDF page 58 · Integrated Furnace Control — Error Codes

    Return to Trane lookup → · Record observations for service →

  17. Code E12

    Open fuse

    Listed S8B1/S8X1 single-stage and S8X2 two-stage cover models only. Exact installed model/revision/control applicability remains unconfirmed; cover model suffixes must be checked in available paperwork.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Error Codes table context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    18-CE16D1-1C-EN · edition April 2021 · printed / PDF page 58 · Integrated Furnace Control — Error Codes

    Return to Trane lookup → · Record observations for service →

If the furnace is not heating, documentation is uncertain or a pattern is unlisted, contact a qualified HVAC professional. Do not open panels, change switches, bypass safeties, reset equipment or test gas/electrical parts using this reference. If you suspect gas leakage or a carbon monoxide hazard, leave the area and contact emergency services or your utility from a safe location.