Rheem furnace fault-code reference

Identify the full manual and furnace-control display context. Similar codes on another furnace or thermostat may have different meanings.

RHEEM / FURNACE / MANUAL-SCOPED PILOT

92-24161-124-03 · (-)96V / (-)(-)96MDV

This reference is limited to the R96V furnace-control Table 20 in document 92-24161-124-03. The cover uses literal families (-)96V / (-)(-)96MDV; that notation is not an automatic model or control match. Check the full manual identifier in available paperwork. Do not open equipment to identify a control.

Open 92-24161-124-03 · cover scope, page 1 → Revision -03, superseding -02; publication date unconfirmed. The owner supplied a distributor-hosted copy, visually inspected here. Direct byte comparison with the manufacturer-hosted edition was unavailable.Open the inspected distributor copy →

Twenty-four selected fault headings from Table 20, printed / PDF pages 109–117. These are alphanumeric tokens at the dual seven-segment furnace control display, not LED flash counts or thermostat alerts. Keep lowercase d1, d4 and d6 distinct from numbers.

Normal-operation Table 19, operating indicator 66 and reset notification 99 are outside this fault lookup. Display orientation matters: if it is uncertain, choose Not sure and ask a qualified professional. Do not operate controls or reset equipment. Code 10 may alternate with another fault; record both existing observations separately.

  1. Code d1

    NO MODEL DATA

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 109 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  2. Code d4

    NO VALID MODEL DATA ON MEMORY CARD

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The source describes this as non-critical and displayed in standby when usable model data remains in the control. This is not an assurance of safe operation.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 109 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  3. Code d6

    HORSEPOWER CONFLICT ON MEMORY CARD

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The source distinguishes the memory-card horsepower conflict from model data retained in the control. This is not an installed motor diagnosis.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 109 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  4. Code 10

    ONE-HOUR LOCKOUT

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The source may alternate 10 with another fault. Record both observed tokens separately; a one-hour label is not an instruction to wait, reset or retry.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 110 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  5. Code 11

    FAILED IGNITION

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The furnace display and communicating thermostat can show this at different stages of repeated ignition failures. This lookup is the furnace-control Table 20, not thermostat alert interpretation.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 110 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  6. Code 12

    LOW FLAME SENSE

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 111 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  7. Code 13

    FLAME LOST AFTER ESTABLISHED

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The furnace display and communicating thermostat can show this at different stages of repeated flame loss. This lookup is the furnace-control Table 20.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 111 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  8. Code 14

    FLAME PRESENT WITH GAS VALVE OFF

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The source labels this extremely critical. Contact a qualified professional; do not reset or attempt service. If gas or carbon monoxide is suspected, leave and contact emergency services or the utility from a safe location.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 111 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  9. Code 22

    MAIN LIMIT OPEN

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 112 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  10. Code 23

    HALC OPEN

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The source states the furnace as configured does not include an HALC control; this row concerns the continuity circuit in that configuration. Do not infer a fitted HALC or perform jumper work.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 112 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  11. Code 26

    LINE AND NEUTRAL REVERSED OR POOR GROUND

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 112 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  12. Code 30

    OPEN FUSE

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 113 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  13. Code 33

    OVER-TEMPERATURE SWITCH (ROLL-OUT) OPEN

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The source describes a serious rollout-limit condition requiring professional investigation. Do not reset or bypass a limit.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 113 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  14. Code 44

    LOW PRESSURE SWITCH CLOSED, INDUCER OFF

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 113 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  15. Code 45

    LOW PRESSURE SWITCH OPEN, INDUCER ON HIGH SPEED

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 114 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  16. Code 46

    LOW PRESSURE SWITCH OPEN, INDUCER ON LOW SPEED

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 114 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  17. Code 55

    HIGH PRESSURE SWITCH CLOSED, INDUCER OFF

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 115 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  18. Code 57

    HIGH PRESSURE SWITCH OPEN, INDUCER ON HIGH SPEED

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 115 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  19. Code 58

    WATER CIRCUIT OPEN

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 115 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  20. Code 59

    WATER SENSED

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 116 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  21. Code 60

    BLOWER FAULT - BLOWER CAN STILL RUN

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The source distinguishes a blower fault that still allows running from code 61. Continued operation does not establish safety.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 116 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  22. Code 61

    BLOWER FAULT - MOTOR CANNOT RUN

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The source distinguishes this non-running blower condition from code 60; the heading alone does not establish a failed part.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 116 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  23. Code 68

    NO BLOWER COMMUNICATIONS

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 117 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

  24. Code 93

    INTERNAL CONTROL FAULT DETECTED

    Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.

    Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.

    Manufacturer-sourced; not reviewed by a qualified technician.

    92-24161-124-03 · revision -03 · printed / PDF page 117 · Table 20 · distributor-hosted copy

    Return to Rheem lookup → · Record observations for service →

If the furnace is not heating, documentation is uncertain or a pattern is unlisted, contact a qualified HVAC professional. Do not open panels, change switches, bypass safeties, reset equipment or test gas/electrical parts using this reference. If you suspect gas leakage or a carbon monoxide hazard, leave the area and contact emergency services or your utility from a safe location.

Prepare observations without a code →