Rheem furnace fault-code reference
Identify the full manual and furnace-control display context. Similar codes on another furnace or thermostat may have different meanings.
RHEEM / FURNACE / MANUAL-SCOPED PILOT
92-24161-124-03 · (-)96V / (-)(-)96MDV
This reference is limited to the R96V furnace-control Table 20 in document 92-24161-124-03. The cover uses literal families (-)96V / (-)(-)96MDV; that notation is not an automatic model or control match. Check the full manual identifier in available paperwork. Do not open equipment to identify a control.
Open 92-24161-124-03 · cover scope, page 1 → Revision -03, superseding -02; publication date unconfirmed. The owner supplied a distributor-hosted copy, visually inspected here. Direct byte comparison with the manufacturer-hosted edition was unavailable.Open the inspected distributor copy →
Twenty-four selected fault headings from Table 20, printed / PDF pages 109–117. These are alphanumeric tokens at the dual seven-segment furnace control display, not LED flash counts or thermostat alerts. Keep lowercase d1, d4 and d6 distinct from numbers.
Normal-operation Table 19, operating indicator 66 and reset notification 99 are outside this fault lookup. Display orientation matters: if it is uncertain, choose Not sure and ask a qualified professional. Do not operate controls or reset equipment. Code 10 may alternate with another fault; record both existing observations separately.
Selected Rheem source entry
Code d1
NO MODEL DATA
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 109 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code d4
NO VALID MODEL DATA ON MEMORY CARD
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The source describes this as non-critical and displayed in standby when usable model data remains in the control. This is not an assurance of safe operation.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 109 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code d6
HORSEPOWER CONFLICT ON MEMORY CARD
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The source distinguishes the memory-card horsepower conflict from model data retained in the control. This is not an installed motor diagnosis.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 109 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 10
ONE-HOUR LOCKOUT
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The source may alternate 10 with another fault. Record both observed tokens separately; a one-hour label is not an instruction to wait, reset or retry.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 110 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 11
FAILED IGNITION
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The furnace display and communicating thermostat can show this at different stages of repeated ignition failures. This lookup is the furnace-control Table 20, not thermostat alert interpretation.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 110 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 12
LOW FLAME SENSE
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 111 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 13
FLAME LOST AFTER ESTABLISHED
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The furnace display and communicating thermostat can show this at different stages of repeated flame loss. This lookup is the furnace-control Table 20.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 111 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 14
FLAME PRESENT WITH GAS VALVE OFF
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The source labels this extremely critical. Contact a qualified professional; do not reset or attempt service. If gas or carbon monoxide is suspected, leave and contact emergency services or the utility from a safe location.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 111 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 22
MAIN LIMIT OPEN
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 112 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 23
HALC OPEN
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The source states the furnace as configured does not include an HALC control; this row concerns the continuity circuit in that configuration. Do not infer a fitted HALC or perform jumper work.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 112 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 26
LINE AND NEUTRAL REVERSED OR POOR GROUND
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 112 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 30
OPEN FUSE
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 113 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 33
OVER-TEMPERATURE SWITCH (ROLL-OUT) OPEN
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The source describes a serious rollout-limit condition requiring professional investigation. Do not reset or bypass a limit.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 113 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 44
LOW PRESSURE SWITCH CLOSED, INDUCER OFF
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 113 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 45
LOW PRESSURE SWITCH OPEN, INDUCER ON HIGH SPEED
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 114 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 46
LOW PRESSURE SWITCH OPEN, INDUCER ON LOW SPEED
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 114 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 55
HIGH PRESSURE SWITCH CLOSED, INDUCER OFF
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 115 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 57
HIGH PRESSURE SWITCH OPEN, INDUCER ON HIGH SPEED
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 115 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 58
WATER CIRCUIT OPEN
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 115 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 59
WATER SENSED
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 116 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 60
BLOWER FAULT - BLOWER CAN STILL RUN
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The source distinguishes a blower fault that still allows running from code 61. Continued operation does not establish safety.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 116 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 61
BLOWER FAULT - MOTOR CANNOT RUN
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match. The source distinguishes this non-running blower condition from code 60; the heading alone does not establish a failed part.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 116 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 68
NO BLOWER COMMUNICATIONS
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 117 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
Selected Rheem source entry
Code 93
INTERNAL CONTROL FAULT DETECTED
Two-stage ECM furnace; literal cover families (-)96V and (-)(-)96MDV; selected table explicitly titled R96V. No wildcard expansion or automatic installed-model/control match.
Manufacturer table heading only, not a confirmed cause or repair instruction. Furnace-control Table 20 context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
92-24161-124-03 · revision -03 · printed / PDF page 117 · Table 20 · distributor-hosted copyReturn to Rheem lookup → · Record observations for service →
If the furnace is not heating, documentation is uncertain or a pattern is unlisted, contact a qualified HVAC professional. Do not open panels, change switches, bypass safeties, reset equipment or test gas/electrical parts using this reference. If you suspect gas leakage or a carbon monoxide hazard, leave the area and contact emergency services or your utility from a safe location.
Prepare observations without a code →