Bryant furnace code reference
Identify the full manual and source context before comparing an already observed pattern.
BRYANT / FURNACE / MANUAL-SCOPED PILOT
SM04-7 · 315AAV / 315JAV
Selected numbered service/status headings for the 315AAV / 315JAV two-stage variable-speed furnace nomenclature on page 3. This does not establish a match for every Bryant furnace or replacement control. Check available paperwork. Do not open equipment to identify a control.
Open SM04-7 · source cover → Manufacturer-controlled shared literature download, visually inspected. SM04-7; copyright imprint 2003 CAC/BDP. Exact publication and revision dates unconfirmed.
Seventeen numbered service/status headings, printed / PDF pages 10–11. The first digit counts short flashes and the second counts long flashes. Preserve the two-digit pattern and service/status context.
The separate component-test table has different interpretations, including code 11. Component-test codes, continuous/rapid states and history-retrieval procedures are excluded. Codes 11 and 12 are history/operating states, not necessarily faults. Do not operate controls to obtain a code.
Selected Bryant source entry
Code 11
NO PREVIOUS CODE
315AAV / 315JAV nomenclature in SM04-7, two-stage variable-speed ECM furnace. Numbered service/status context only; not the separate component-test table. No exact installed-control match confirmed. This heading describes a history/operating state, not necessarily an equipment fault.
Manufacturer table heading only, not a confirmed cause or repair instruction. Service/Status Code Instructions table context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
SM04-7 · printed / PDF page 10 · Service/Status Code Instructions · manufacturer-hosted copyReturn to Bryant lookup → · Record observations for service →
Selected Bryant source entry
Code 12
BLOWER ON AFTER POWER UP
315AAV / 315JAV nomenclature in SM04-7, two-stage variable-speed ECM furnace. Numbered service/status context only; not the separate component-test table. No exact installed-control match confirmed. This heading describes a history/operating state, not necessarily an equipment fault.
Manufacturer table heading only, not a confirmed cause or repair instruction. Service/Status Code Instructions table context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
SM04-7 · printed / PDF page 10 · Service/Status Code Instructions · manufacturer-hosted copyReturn to Bryant lookup → · Record observations for service →
Selected Bryant source entry
Code 13
LIMIT CIRCUIT LOCKOUT
315AAV / 315JAV nomenclature in SM04-7, two-stage variable-speed ECM furnace. Numbered service/status context only; not the separate component-test table. No exact installed-control match confirmed.
Manufacturer table heading only, not a confirmed cause or repair instruction. Service/Status Code Instructions table context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
SM04-7 · printed / PDF page 10 · Service/Status Code Instructions · manufacturer-hosted copyReturn to Bryant lookup → · Record observations for service →
Selected Bryant source entry
Code 14
IGNITION LOCKOUT
315AAV / 315JAV nomenclature in SM04-7, two-stage variable-speed ECM furnace. Numbered service/status context only; not the separate component-test table. No exact installed-control match confirmed.
Manufacturer table heading only, not a confirmed cause or repair instruction. Service/Status Code Instructions table context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
SM04-7 · printed / PDF page 10 · Service/Status Code Instructions · manufacturer-hosted copyReturn to Bryant lookup → · Record observations for service →
Selected Bryant source entry
Code 15
BLOWER MOTOR LOCKOUT
315AAV / 315JAV nomenclature in SM04-7, two-stage variable-speed ECM furnace. Numbered service/status context only; not the separate component-test table. No exact installed-control match confirmed.
Manufacturer table heading only, not a confirmed cause or repair instruction. Service/Status Code Instructions table context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
SM04-7 · printed / PDF page 10 · Service/Status Code Instructions · manufacturer-hosted copyReturn to Bryant lookup → · Record observations for service →
Selected Bryant source entry
Code 21
GAS HEATING LOCKOUT
315AAV / 315JAV nomenclature in SM04-7, two-stage variable-speed ECM furnace. Numbered service/status context only; not the separate component-test table. No exact installed-control match confirmed.
Manufacturer table heading only, not a confirmed cause or repair instruction. Service/Status Code Instructions table context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
SM04-7 · printed / PDF page 10 · Service/Status Code Instructions · manufacturer-hosted copyReturn to Bryant lookup → · Record observations for service →
Selected Bryant source entry
Code 22
ABNORMAL FLAME-PROVING SIGNAL
315AAV / 315JAV nomenclature in SM04-7, two-stage variable-speed ECM furnace. Numbered service/status context only; not the separate component-test table. No exact installed-control match confirmed.
Manufacturer table heading only, not a confirmed cause or repair instruction. Service/Status Code Instructions table context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
SM04-7 · printed / PDF page 10 · Service/Status Code Instructions · manufacturer-hosted copyReturn to Bryant lookup → · Record observations for service →
Selected Bryant source entry
Code 23
PRESSURE SWITCH DID NOT OPEN
315AAV / 315JAV nomenclature in SM04-7, two-stage variable-speed ECM furnace. Numbered service/status context only; not the separate component-test table. No exact installed-control match confirmed.
Manufacturer table heading only, not a confirmed cause or repair instruction. Service/Status Code Instructions table context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
SM04-7 · printed / PDF page 10 · Service/Status Code Instructions · manufacturer-hosted copyReturn to Bryant lookup → · Record observations for service →
Selected Bryant source entry
Code 24
SECONDARY VOLTAGE FUSE IS OPEN
315AAV / 315JAV nomenclature in SM04-7, two-stage variable-speed ECM furnace. Numbered service/status context only; not the separate component-test table. No exact installed-control match confirmed.
Manufacturer table heading only, not a confirmed cause or repair instruction. Service/Status Code Instructions table context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
SM04-7 · printed / PDF page 10 · Service/Status Code Instructions · manufacturer-hosted copyReturn to Bryant lookup → · Record observations for service →
Selected Bryant source entry
Code 25
MODEL SELECTION OR SETUP ERROR
315AAV / 315JAV nomenclature in SM04-7, two-stage variable-speed ECM furnace. Numbered service/status context only; not the separate component-test table. No exact installed-control match confirmed.
Manufacturer table heading only, not a confirmed cause or repair instruction. Service/Status Code Instructions table context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
SM04-7 · printed / PDF page 10 · Service/Status Code Instructions · manufacturer-hosted copyReturn to Bryant lookup → · Record observations for service →
Selected Bryant source entry
Code 31
HIGH-HEAT PRESSURE SWITCH OR RELAY DID NOT CLOSE OR REOPENED
315AAV / 315JAV nomenclature in SM04-7, two-stage variable-speed ECM furnace. Numbered service/status context only; not the separate component-test table. No exact installed-control match confirmed.
Manufacturer table heading only, not a confirmed cause or repair instruction. Service/Status Code Instructions table context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
SM04-7 · printed / PDF page 10 · Service/Status Code Instructions · manufacturer-hosted copyReturn to Bryant lookup → · Record observations for service →
Selected Bryant source entry
Code 32
LOW-HEAT PRESSURE SWITCH DID NOT CLOSE OR REOPENED
315AAV / 315JAV nomenclature in SM04-7, two-stage variable-speed ECM furnace. Numbered service/status context only; not the separate component-test table. No exact installed-control match confirmed.
Manufacturer table heading only, not a confirmed cause or repair instruction. Service/Status Code Instructions table context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
SM04-7 · printed / PDF page 10 · Service/Status Code Instructions · manufacturer-hosted copyReturn to Bryant lookup → · Record observations for service →
Selected Bryant source entry
Code 33
LIMIT CIRCUIT FAULT
315AAV / 315JAV nomenclature in SM04-7, two-stage variable-speed ECM furnace. Numbered service/status context only; not the separate component-test table. No exact installed-control match confirmed.
Manufacturer table heading only, not a confirmed cause or repair instruction. Service/Status Code Instructions table context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
SM04-7 · printed / PDF page 10 · Service/Status Code Instructions · manufacturer-hosted copyReturn to Bryant lookup → · Record observations for service →
Selected Bryant source entry
Code 34
IGNITION PROVING FAILURE
315AAV / 315JAV nomenclature in SM04-7, two-stage variable-speed ECM furnace. Numbered service/status context only; not the separate component-test table. No exact installed-control match confirmed.
Manufacturer table heading only, not a confirmed cause or repair instruction. Service/Status Code Instructions table context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
SM04-7 · printed / PDF page 10 · Service/Status Code Instructions · manufacturer-hosted copyReturn to Bryant lookup → · Record observations for service →
Selected Bryant source entry
Code 41
BLOWER MOTOR FAULT
315AAV / 315JAV nomenclature in SM04-7, two-stage variable-speed ECM furnace. Numbered service/status context only; not the separate component-test table. No exact installed-control match confirmed.
Manufacturer table heading only, not a confirmed cause or repair instruction. Service/Status Code Instructions table context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
SM04-7 · printed / PDF page 11 · Service/Status Code Instructions · manufacturer-hosted copyReturn to Bryant lookup → · Record observations for service →
Selected Bryant source entry
Code 43
LOW-HEAT PRESSURE SWITCH OPEN WHILE HIGH-HEAT PRESSURE SWITCH IS CLOSED
315AAV / 315JAV nomenclature in SM04-7, two-stage variable-speed ECM furnace. Numbered service/status context only; not the separate component-test table. No exact installed-control match confirmed.
Manufacturer table heading only, not a confirmed cause or repair instruction. Service/Status Code Instructions table context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
SM04-7 · printed / PDF page 11 · Service/Status Code Instructions · manufacturer-hosted copyReturn to Bryant lookup → · Record observations for service →
Selected Bryant source entry
Code 45
CONTROL CIRCUITRY LOCKOUT
315AAV / 315JAV nomenclature in SM04-7, two-stage variable-speed ECM furnace. Numbered service/status context only; not the separate component-test table. No exact installed-control match confirmed.
Manufacturer table heading only, not a confirmed cause or repair instruction. Service/Status Code Instructions table context only; exact unit/control applicability remains unconfirmed.
Manufacturer-sourced; not reviewed by a qualified technician.
SM04-7 · printed / PDF page 11 · Service/Status Code Instructions · manufacturer-hosted copyReturn to Bryant lookup → · Record observations for service →
If the furnace is not heating, documentation is uncertain or a pattern is unlisted, contact a qualified HVAC professional. Do not open panels, change switches, bypass safeties, reset equipment or test gas/electrical parts using this reference. If you suspect gas leakage or a carbon monoxide hazard, leave the area and contact emergency services or your utility from a safe location.
Prepare observations without a code →